Two machines, one house
The September 3, 2026 Dependable Grid terms describe dual fuel as an efficient electric heat pump paired with a non-electric system “to help keep buildings warm during extreme cold while reducing pressure on the electrical grid during winter peaks.” The non-electric side is oil, propane, or wood. It may already be in the building. It does not have to be bought with the heat pump. Terms, dual-fuel section
The eligible building is one that is primarily electric now, or a new home that would have been. A house whose only backup is electric baseboard is not this rebate’s dual-fuel system. A house whose primary heat is already oil is a different stream. The terms define primary heat as the permanent system sized to hold 22°C at the 2.5% January design temperature in National Building Code Table C-2. A cordwood stove or fireplace does not qualify as that primary system. Terms
What “balance point” means
NRCan calls the thermal balance point the outdoor temperature where the heat pump’s heating capacity equals the house’s heat loss. Above it, the heat pump can meet the load alone. Below it, the heat pump covers only part of the heat and supplementary heat is required. NRCan separates that from the minimum operating temperature, where the machine stops entirely. The same guide puts that cutoff, for many air-source units, somewhere from about −15°C to −25°C. NRCan heat pump guide
Yukon adds a number the listing test does not use. The heat pump must be sized to heat the entire building and achieve a balance point of −20°C or colder. Terms That is not NRCan’s cold-climate test, which is scored at −15°C. It is also not the design temperature. Whitehorse’s January 2.5% value in the NRC climatic tables is −41°C. NRC tables The rebate does not require the heat pump to carry the house alone at −41°C. It requires the machine to still match the heat loss at −20°C or colder, with oil, propane, or wood covering everything colder than that, plus any hour the heat pump is off.
When each one runs
| Outdoor condition | Heat pump | Oil, propane, or wood |
|---|---|---|
| Warmer than the balance point | Can meet the whole heating load. | Idle, unless you choose to run it for another reason. |
| Colder than the balance point, but above the heat pump’s cutoff | Still runs, and covers only part of the load. | Makes up the difference. |
| At or below the heat pump’s cutoff | Stops. | Is the heat. |
| Defrost | Briefly stops delivering heat indoors while it melts the outdoor coil. | May be called to cover that pause. NRCan treats supplementary heat as part of a proper defrost strategy. |
| Power outage | Off, unless you have generation sized for it. | Has to be able to run. See the note below. |
The temperature bands are NRCan’s description of how a heat pump and supplementary heat share a load. NRCan The −20°C floor on the balance point is the Yukon rule, not an NRCan rule. Terms
There is a second switch, and it is about money. NRCan describes an economic balance point: the outdoor temperature where the backup fuel becomes cheaper per unit of heat than running the heat pump. The Yukon terms do not set that temperature. They require the heat pump to be capable of a −20°C balance point. Whether you switch the backup on earlier, because a particular hour of electricity is expensive, is an operating choice. It is not what the rebate measures.
Which backup actually counts
- Oil, propane, or wood. Electric resistance does not satisfy the dual-fuel backup.
- If the backup needs electricity — an oil furnace fan, a propane furnace, a wood furnace with a blower — it must plug into a standard outlet the terms call “110-volt,” or sit on a transfer switch, so a generator can feed it. A wood stove with no fan does not have that requirement.
- A propane fireplace has to be on NRCan’s product list at 75 percent efficiency or higher.
- Wood equipment has to be EPA-certified and meet EPA NSPS or CSA B415.10. Particulate caps in the terms: 2.5 grams per hour for cordwood stoves, pellet stoves, and inserts; 0.10 lb/MMBtu for wood boilers, or 0.15 if tested on cordwood; 0.15 lb/MMBtu for wood furnaces.
An air-source heat pump in this rebate also has to be on NRCan’s cold-climate list for Manitoba and Yukon. A ground-source unit has to be ENERGY STAR. The list is a performance screen. The balance point is a house calculation. Both are required. Terms
Related pages
- 01 Overview
What a cold-climate heat pump is, and what this guide will and will not claim.
- 03 Dependable Grid rebate
Dual fuel and the other Dependable Grid amounts, from the September 3, 2026 terms.
- 04 Good Energy rebate
The other heat pump rebate: 50 percent up to $10,500 on an existing home, $1,500 on a new one.
- 05 Affordable Heat Pump Program
100 percent up to $24,000 for an income-qualified home. Pre-approval. Not stackable with the other two.
Sources
Every figure on this page comes from the documents below. If a later official update conflicts, the official update wins.
- Yukon energy incentive terms (PDF)
September 3, 2026. Dual-fuel definition, eligible buildings, −20°C balance point, oil/propane/wood backup rules, wood emission caps, and the 110-volt or transfer-switch requirement.
- Heating and cooling with a heat pump
NRCan. Thermal balance point, economic balance point, minimum operating temperature, and supplementary heat during defrost.
- NRC climatic tables
Whitehorse January 2.5% design temperature −41°C. The rebate’s −20°C balance point is not this design temperature.